Report catalogue
WS.PEMS makes two kinds of reports. A template report is a table: one column per tag or emission, one row per interval. A composed report is a document with pages, sections, tables and text. It uses one or more template reports as its data. You can make your own templates and compositions. This page lists the ones that WS.PEMS ships with.
A template report can export each table to a separate file in one ZIP file.
Report results per period
A compliance report can include report results: counts, lists and percentages that the reporting regulations ask for. When you create a report, WS.PEMS selects default results for the period of the report. "Yes" marks a result selected by default in a new installation. Your installation can use different defaults. You can add or remove results.
| Result | Description | Daily | Weekly | Monthly | Yearly |
|---|---|---|---|---|---|
NumberSTAReportableMode | Number of STA in reportable mode. (Quality != 99) | Yes | Yes | Yes | Yes |
NumberSTAInvalided | Number of STA invalided (Quality < 100) | Yes | Yes | Yes | Yes |
NumberSTA | Number of STA periods in the reporting period | Yes | Yes | Yes | Yes |
ListOfVstaWithTags | List of all VSTA values and tags | Yes | |||
NumberVSTAExceedingELV | Number of VSTA exceeding the ELV | Yes | Yes | Yes | Yes |
ListOfDailyLta | List of daily LTA | Yes | Yes | Yes | |
NumberInvalidDays | Number of invalid days according to relevant legislation | Yes | Yes | Yes | Yes |
MalfunctioningOrBreakdownAbatementEquipment | List of all periods of malfunctioning or breakdown of abatement equipment and unabated operation | Yes | |||
ListOfLtaOtherThanDay | List of LTA for periods other than a day | Yes | Yes | Yes | |
NumberLTAExceedingELV | Number of LTA exceeding the ELV | Yes | Yes | Yes | |
NumberInvalidDaysYear | Number of invalid days according to relevant legislation since 1st of January of the current year | Yes | Yes | Yes | Yes |
PercentSSTAExceedingCalibrationRange | Percentage of SSTA exceeding the valid calibration range according to EN 14181 | Yes | Yes | Yes | |
HoursMalfunctioningOrBreakdownAbatementEquipment | Number of hours of malfunctioning or breakdown of abatement equipment and unabated operation in a rolling 12 month period | Yes | Yes | Yes | Yes |
NumberPeriodsMalfunctioningOrBreakdownAbatementEquipment | Number of periods with more than legislative allowed period of malfunctioning or breakdown of abatement equipment and unabated operation since 1st January | Yes | |||
SSTA5 | Number of weeks with more than 5% of the SSTA exceeding the valid calibration range since the last QAL2 or AST (calibration), Quality = 102 | Yes | |||
SSTA40 | Number of weeks with more than 40% of the SSTA exceeding the valid calibration range since the last QAL2 or AST (calibration), Quality = 102 | Yes | |||
PercentVSTAExceedingELV | Percentage of VSTA exceeding the ELV since 1st of January of the current year. | Yes | Yes | ||
PercentLTAExceedingELV | Percentage of LTA exceeding the ELV since 1st of January of the current year. | Yes | Yes | ||
NumberSTAContainingCappedFLD | Number of STA containing capped FLD | Yes | |||
NumberSTAContainingFLDExceedingRange | Number of STA containing FLD exceeding the measurement range | Yes | |||
NumberSSTACalculatedUsingSubstituteValues | Number of SSTA calculated using substitute values | Yes | Yes | ||
TotalMassEmission | Total mass emission | Yes | |||
NumberSubstituteValuesUsedForCalculationOfMassEmission | Number of substitute values used for the calculation of the mass emissions | Yes | |||
PercentOfFldCapped | Percent of Fld capped |
Composed report examples
The examples below are composed report definitions in YAML. They show how to build a report for a regulation or a type of site. Each one needs the template and column ids of your installation before you can use it. Composed reports need the composed reports feature to be turned on.
| Report | What it covers | Period | Output formats | Layout |
|---|---|---|---|---|
| Annual NOx and operating hours report for a dual-fuel gas turbine site | Totals for the period and per month: operating hours per fuel (gas, diesel, mixed, unaccounted and OTNOC), fuel energy, gas volume, diesel mass, NOx mass, total energy and apparent NOx. Per emission source: a daily heat input chart and daily NOx against the emission limit value for gas and for diesel. | Year, up to a cutoff date that you select | CSV, Excel, HTML, PDF | A4 landscape page, 4 sections, with sections repeated per month and emission source |